Brand Name : Acrel
Model Number : AIM-T500
Certification : ISO/CE
Place of Origin : Jiangsu, China
MOQ : 1
Price : USD 1850 pcs
Payment Terms : L/C, T/T
Supply Ability : 6000000 pcs per year
Delivery Time : 5-8 work days
Packaging Details : 17X16X15 cm
Communication : RS485 Modbus-RTU
Display : LCD
Applicable System Voltage Range : Up to 800V (AC DC AC&DC)
Auxiliary Power : AC 85-265V
Frequency : 40-60Hz
Alarm Range : 10kΩ-10MΩ
| Auxiliary power | Voltage | AC 85-265V DC 120-370V |
| Frequency | 50/60HZ | |
| Insulation monitoring | Range of the insulation measurement | 1k-10M^Ω |
| Early warning and alarm range | 10k-10M^Ω | |
| Response time(Ce=luF) | <5s | |
| Measuring voltage | <50V | |
| Allowable system leakage capacitance | <500uF | |
| Internal parameters | Measuring current | <270uA |
| Internal DC impedance | >180k^Ω | |
| Power dissipation | <8W | |
| Suitable voltage class | System voltage | AC 0~800V DC 0~690V |
| frequency range | 40~460HZ | |
| Output | Relay output | Error, warning, alarm |
| Environment | Working temperature | (-15 ~ +55℃) |
| Storage temperature | (-20~+70℃) | |
| Relative humidity | 5%-90%, no dew | |
| Altitude | <2500m | |
| Communication | RS485, Modbus-RTU protocol | |
| Rated impulse voltage/class of pollution | 8kV/III | |
| EMC electromagnetic compatibility/electromagnetic radiation | Conform to IEC61326-2-4 | |



|
|
AIM-T500 Industrial Isolated Power System Insulation Monitor Device 40-60Hz Images |